- All
- Product Management
- News
- Introduction
- Enterprise outlets
- FAQ
- Enterprise Video
- Enterprise Atlas
Company Products
FC726-GQ and FC726-GQ/M cabinet controllers
Product Description
Features:
• Modular, redundant safety design concept.
• Full Chinese menu operation, supports local and network event display operations, clear and intuitive.
• Supports custom buttons for easy operation.
• Large storage space, can record up to 7000 records.
• The controller has 2 remote fire alarm outputs, one passive output and one monitored active output.
• The controller has 2 remote fault outputs, one passive output and one monitored active output.
• The controller has 1 monitored sound and light alarm output (24VDC).
• The controller has a 32-channel linkage panel that can be expanded to a maximum of 64 channels (output: 40mA @24VDC) for manual control of important equipment.
• The system adopts "AND", "OR" and "NOT" linkage programming methods to realize complex linkage programming requirements.
• Can realize network of 64 controllers (C-WEB/SAFEDLINK/ETHERNET).
• Network bus (C-WEB/SAFEDLINK), it is recommended to use flame-retardant twisted pair wires with Ø ≥ 1.0 mm2, with a maximum distance of 1000m (cable star connection). Reachable (single mode) 40000m through dedicated optical fiber module. Backbone network networking, the longest distance between each network node can reach 3000 meters.
• The field component bus (C-NET) has polarity for both buses. It is recommended to use flame-retardant twisted pair wires with Ø ≥ 1.0mm2, flame-retardant twisted pair wires, the total loop length is 5000 meters, and the furthest point of the line is 4280 meters.
• The controller supports 3-level user operations and is protected by password to ensure different operations under different user levels.
• Automatically map devices to facilitate debugging.
• Supports multiple early warnings; fire alarms and other fire danger levels.
• Remote download and management.
• Supports ASAtechnology fire detection technology, automatically adapts to environmental changes, and greatly improves detection reliability.
• On-site components come with tear-off coding stickers to facilitate engineering debugging.